Journal of Applied Electrochemistry, Vol.41, No.10, 1167-1174, 2011
Simulation and optimization of a flow battery in an area regulation application
Flow batteries have the potential to provide ancillary grid services such as area regulation. In this paper, a hypothetical 2 MW flow battery is simulated in an area regulation application to find the optimal energy-to-power ratio that maximizes the net present value (NPV) of a 10 year project based on a range of installation costs. Financial and operational results are presented, and candidate battery chemistries are discussed. A simplified model of battery installation costs (dollars per kW h) resulted in a positive NPV for installation costs below $500 kW(-1) h(-1). For installation costs between $300 and $500 kW(-1) h(-1), an optimal energy-to-power ratio is 1.39. The traditional advantage of decoupling power and energy capacity may not be realized in area regulation; therefore hybrid flow batteries may be more appropriate. Zinc-bromine and iron-chromium chemistries might fit well with this application, along with lower-cost flow battery chemistries in the future.