화학공학소재연구정보센터
International Journal of Heat and Mass Transfer, Vol.50, No.21-22, 4256-4264, 2007
Condensation heat transfer and pressure drop of R134a in annular helicoidal pipe at different orientations
Experimental investigations were conducted to determine the condensation heat transfer and pressure drop of refrigerant R134a in annular helicoidal pipe at three inclination angles. The experiments were performed with the Reynolds number of R 134a ranging from 60 to 200, and that of cooling water from 3600 to 22 000; temperatures of R134a at 30 degrees C and 35 degrees C, and cooling water at 16 degrees C, 20 degrees C and 24 degrees C. The experimental results indicated that the refrigerant Nusselt number was larger at lower refrigerant saturation temperature, and would increase with the increase of mass flow rates of refrigerant and cooling water. It was found that the refrigerant heat transfer coefficient of annular helicoidal pipe could be two times larger than that of equivalent plain straight pipe when the refrigerant Reynolds number was larger than 140. Comparison with identical helicoidal pipe with opposite flow channel arrangement revealed that the refrigerant heat transfer rate was larger when the refrigerant was flowing in the annular section at the cooling water Reynolds number larger than 4000, but the pressure drop was always larger in this flow channel arrangement. Published by Elsevier Ltd.