- Previous Article
- Next Article
- Table of Contents
International Journal of Heat and Mass Transfer, Vol.48, No.12, 2351-2359, 2005
Evaporating heat transfer and pressure drop of hydrocarbon refrigerants in 9.52 and 12.70 mm smooth tube
Experimental results of heat transfer characteristic and pressure gradients of hydrocarbon refrigerants R-290, R-600a, R-1270 and HCFC refrigerant R-22 during evaporating inside horizontal double pipe heat exchangers are presented. The test sections have one tube diameter of 12.70 mm with 0.86 mm wall thickness, another tube diameter of 9.52 turn with 0.76 mm wall thickness was used for this study. The local evaporating heat transfer coefficients of hydrocarbon refrigerants were higher than those of R-22. The average evaporating heat transfer coefficient increased as the mass flux increased. It is showed the higher values in hydrocarbon refrigerants than R-22. Comparing the heat transfer coefficient of experimental results with that of other correlations, the obtained results from the experiments had coincided with most of the Kandlikar's correlation. Hydrocarbon refrigerants have higher pressure drop than R-22 in 12.7 mm and 9.52 mm. This results form the study can be used in the case of designing heat transfer exchangers using hydrocarbons as the refrigerant for the air-conditioning systems. (c) 2005 Elsevier Ltd. All rights reserved.
Keywords:hydrocarbon refrigerant;evaporation;heat transfer coefficient;pressure drop;natural refrigerant