International Journal of Heat and Mass Transfer, Vol.131, 1164-1173, 2019
Analytical heat transfer model for laterally perforated-finned heat sinks
An analytical model is proposed to predict the average Nusselt numbers of laterally perforated-finned heat sinks (LA-PFHSs) with high aspect ratios in forced convection laminar flows. The model is developed based on the experimental data acquired from testing air-cooled heat sinks including square cross-sectional perforations distributed equidistantly along the length of the fins. The experiments were conducted using three different perforation sizes and five different porosities at each perforation size. The accuracy of the experiments was validated by comparing the experimental pressure drops and heat transfer coefficients of the heat sink without perforation with those obtained from the widely accepted correlations in the literature. The developed model in this study predicts the Nusselt number as a function of Reynolds number, Prandtl number, fin and perforation geometrical parameters, porosity, and the distances between perforations. The model showed excellent predictions for the Nusselt numbers of all LA-PFHSs tested in this study to be within +/- 12% of the experimental data and a mean absolute error of 4.90%. This study is the first attempt in the literature to develop an analytical model based on experimental data for investigating heat transfer in LA-PFHSs. (C) 2018 Elsevier Ltd. All rights reserved.
Keywords:Air-cooled heat sink;Perforated fin;Boundary layer interruption;Analytical model;Nusselt number