Energy and Buildings, Vol.183, 592-606, 2019
Influences of the mixed LiCl-CaCl2 liquid desiccant solution on a membrane-based dehumidification system: Parametric analysis and mixing ratio selection
The membrane-based liquid desiccant dehumidification system has high energy efficiency without the traditional liquid system carry-over problem. The performance of such a system strongly depends on solution's temperature and concentration, which have direct relationship to the solution surface vapour pressure. Compared with the pure liquid desiccant solution, the mixed liquid desiccant solution has lower surface vapour pressure, better system performance and lower material cost. In this paper, the performance of a flat-plate membrane-based liquid desiccant dehumidification system with the mixed solution (LiCl and CaCl2) is investigated through theoretical and experimental approaches. A mathematical model is established to predict the system performance, while the electrolyte non-random two-liquid (NRTL) method is applied to calculate the mixed solution properties. The influences of the solution mixing ratio, temperature T-sol and concentration C-sol are evaluated, and it is found that the regeneration heat Q(reg) can be dramatically reduced by either applying a high concentration solution or increasing CaCl2 content in the mixed solution. Compared with the pure LiCl solution system, the mixed solution system COP can be improved up to 30.23% by increasing CaCl2 content for a 30% concentration solution. The optimum mixing ratio varies with the solution concentration. For the mixed LiCl-CaCl2 solution, the system highest COPs appear at the mixing ratios of 3:1, 2:1 and 1:1 for 20%, 30% and 40% concentrations respectively. (C) 2018 Elsevier B.V. All rights reserved.