International Journal of Heat and Mass Transfer, Vol.111, 29-40, 2017
Geyser boiling phenomenon in two-phase closed loop-thermosyphons
Geyser boiling is experimentally investigated in two-phase closed loop-thermosyphons, consisting of two parallel condensers and a shared evaporator. Heat sink conditions at each condenser vary from forced to natural convection in a multitude of thermal arrangements. A cartridge resistance provides input power ranging from 0.1 to 0.85 kW to the evaporator. Water is employed as working fluid with filling ratios of 0.5 and 0.9. The effects of thermal conditions in both condensers, filling ratio, heat flux and vapor pressure on geyser boiling phenomenon are investigated. Geyser boiling eventually yields intense evaporator vibrations inferred by acceleration measurements. The ratio of convective thermal resistances acting at each condenser affects the acceleration. Amplitudes up to 110 and 1100 m/s(2) were observed for filling ratios of 0.5 and 0.9, respectively. In unsteady regime, geysering occurs for heat fluxes less than 20 kW/m(2) and vapor pressures less than 25 kPa. The vapor pressure is increased with increasing heat flux, suppressing geyser boiling intensity. In steady-state regime geyser boiling occurs for heat fluxes higher than 12.5 kW/m(2) and vapor pressures below 25 kPa. (C) 2017 Elsevier Ltd. All rights reserved.
Keywords:Geyser boiling;Loop-thermosyphons;Acceleration measurements;Thermal resistance;Heat sinks;Filling ratio