Energy and Buildings, Vol.146, 182-199, 2017
Development of a new multi-stage building energy model calibration methodology and validation in a public library
Calibration of a Building Energy Model (BEM) is necessary to reduce the discrepancies between the simulation results and real data. This research work proposes a novel ground-breaking calibration methodology that divides the entire building into different sub-models and calibrates them separately to obtain an accurate model. To validate this new procedure, a public library Heating, Ventilation and Air Conditioning (HVAC) system with a Ground-Source Heat Pump (GSHP) and a Radiant Floor (RF) was simulated and calibrated using TRNSYS and GenOpt. The results demonstrated that this new multi-stage procedure met the ASHRAE standards and achieved better results than those obtained with a global calibration. The Mean Bias Error (MBE) and the Coefficient of Variation of the Root Mean Square Error (CV(RMSE)) of the hourly temperature data were reduced below 3.74% and 6.03% respectively, involving an improvement of approximately 50% over typical global calibration methods. (C) 2017 Elsevier B.V. All rights reserved.
Keywords:Multi-stage calibration;Building energy model;TRNSYS;GenOpt;ASHRAE guideline 14;Ground-Source;Heat pump;Radiant floor