Solar Energy, Vol.83, No.12, 2186-2194, 2009
A novel solar bi-ejector refrigeration system and the performance of the added injector with different structures and operation parameters
A novel solar bi-ejector refrigeration system was investigated, whose difference compared to the traditional system is that the circulation pump is replaced by a thermal injector. The new system works more stably and needs less maintenance work than the old one, and the whole system can more fully utilize the solar energy. The mathematical models for calculating the performance of the injector and the whole solar refrigeration system were established. The pressure rise performance of injector under different structure and operation parameters and the performance of solar bi-ejector refrigeration system were studied with R123. The results show that the discharged pressure of injector is affected by structure dimensions of injector and operation conditions. With increasing generation temperature, the entrainment ratio of ejector becomes better while that of injector becomes worse and the overall thermal efficiency of the solar bi-ejector refrigeration system first increases and then decreases with an optimum value of 0.132 at generation temperature of 105 degrees C, condensation temperature of 35 degrees C and evaporation temperature of 10 degrees C. (C) 2009 Elsevier Ltd. All rights reserved.