Energy and Buildings, Vol.52, 56-67, 2012
Hydronic circuit topologies for thermally activated building systems -design questions and case study
For proper implementation of thermally activated building systems (TABS), control strategy and hydronic circuit topology, which take into account the large, thermal time constant of TABS, are required. It is shown that hydronic topology is strongly related to the division into TABS zones and the additional control system at an individual room level. In this article, results from measurements of two buildings with advanced hydronic circuit topology are presented. From the results, it can be concluded that, in order to meet thermal comfort requirements, TABS should be divided into several zones. For zone division, differences in both external and internal heat loads should be taken into account. The required hydronic circuit topology to supply warm and cold water to each TABS zone can be simplified into two distribution pipes that have the ability to disconnect from the central water supply but do not have the ability to allow circulation. Furthermore, the measurements show that with an appropriate control strategy the issue of energy squandering within TABS can be eliminated. (C) 2012 Elsevier B.V. All rights reserved.
Keywords:Thermally activated building systems (TABS);Thermal comfort;Design questions;Energy efficiency;Hydronic circuit topology;Control strategy;Case study;Energy squandering