Energy, Vol.50, 205-219, 2013
No-load loss calculation of distribution transformers supplied by nonsinusoidal voltage using three-dimensional finite element analysis
Transformers are basically designed to operate under nominal voltage, rated frequency and also, pure sinusoidal load current. In recent decade, change in the type of loads and increasing use of power electronic devices with their nonsinusoidal current waveform has distorted the system voltage waveform as well. The losses of transformers include load and no-load losses. No-load loss continuously led to loss of energy in transformers that are connected to the network in all 24 h. With respect to high significance of energy and undesirable impacts of losses on the aging of transformers, the no-load loss is considered as a critical factor. Nowadays, it is necessary to apply a suitable method for calculation of no-load loss in presence of the voltage harmonics and over-excite conditions, especially for distribution transformers, as a result of harmonic increase in the voltage and current in the network and particular applications. In this paper, Finite Element Method (FEM) has been used to simulate nonsinusoidal voltage effects on no-load loss of transformers. Such simulation enables the software to simulate and analyze different electromagnetic parameters such as flux lines, flux density, losses, and etc under different input sources and with high accuracy. In addition, effect of nonsinusoidal voltages on no-load loss has been investigated by a typical experimental transformer using several practical tests. (C) 2012 Elsevier Ltd. All rights reserved.